Precision Measurement Engineering, Inc.
Discussing SCAMP Maintenance
REPLACING A SENSOR
- Drain and remove the sensor cover.
- Open the SCAMP. See Opening
the SCAMP section for more detailed information. This is a delicate operation
since the sensors are exposed at this time. Insure no residual water droplets run
down into the electronics region.
- Clamp the SCAMP electronics horizontally in two vises
by clamping the chassis, not the electronics covers. The sensor being replaced should be
up. The following pictures show the Fast Temperature sensor (5316) with its
associated resistor. Use two vises. If one vise is used, and the SCAMP
clamped in the middle, it will unexpectedly slip and rotate the sensors into the table
top.
- Remove the electronics cover. See Removing and Replacing the Electronics Covers section for more
detailed information.

- Cut the wires from the sensor being replaced so that
1/4" of colored insulator remain attached to the post. This will indicate the proper
wiring of the new sensor. Click on the picture for a more detailed image.

- Use the pliers to gently unscrew (counter clockwise
seen from the sensor side) the sensor sealing nut. Slide this nut up the sensor shaft.

- Loosen the set screw in the chassis end plate that
mechanically retains the sensor.

- Rotate the sensor so that it is not near the other
sensors.

- Gently pull the sensor out of the endcap being careful
that the wires don't crash the other sensors.. Place a protective cover on it.

- Installing the new sensor. Inspect
the wires-end of the shaft to make sure that there are no burrs, glue, other foreign
materials, or scratches in the area where the seal is made. Remove the plastic thermistor
cover. This is a very delicate operation!! Place the retaining nut on the
shaft. The image below shows a Fast Temperature sensor.

- Gently slide the sensor into the endcap.

- Position the sensor properly. You may be required to
bend the sensor shaft somewhat if close alignment is desired. Tighten the set screw when
this is accomplished.


- Tighten the sealing nut firmly with pliers. CAREFUL! THE RETAINING NUT MAY SHIFT THE SENSOR POSITION SLIGHTLY
OR TWIST THE SENSOR IF THE RETAINING SCREW IS NOT TIGHT CAUSING THE SENSOR TO CRASH INTO
THE OTHERS.

- Cut the sensor wires to the appropriate length (leave
a long loop) and strip the last 1". New sensors should already have the wires
stripped at the correct length. If a wire must be stripped and the proper 30 gauge
stripping tool is unavailable the insulation can be removed by melting through it with a
soldering iron while pulling on the wire. One at a time unwind the old sensor wire
and replace it with the same color new sensor wire. Remember when replacing the Fast
Temperature sensor that there is a resistor to replace as well. Use the wire
wrapping tool supplied by PME to wire wrap the new wires. DO NOT SOLDER!

- Replace the electronics cover. See Removing and Replacing the Electronics Covers section for more
detailed information.

- Examine the o-rings as described in the Inspecting the O-rings section.
- Insert the SCAMP electronics back into the tube until
the o-rings engage.

- Replace the closure ring and tighten it, pulling
the SCAMP electronics completely into the tube. Only tighten this ring until the
electronics are completely in the tube. Loosen the ring slightly so that it will be
easy to unscrew at a later date.

- Replace the sensor cover.
Pressurize the interior as described in the leak test, then
partially fill the sensor cover with water. Carefully check for bubbles exiting
between the sealing nut and sensor shaft.. If bubbles appear, then drain and remove the
cover. Re-tighten the sealing nut. This nut is only plastic so don't tighten it too
much. Repeat the leak test.

- If bubbles persist, then follow the above steps to remove
the sensor. Inspect the sensor shaft. Remove the teflon ferrule within the endcap hole and
replace it. Repeat the procedure.
- Now that the sensor is physically installed on the SCAMP, its
calibration must be installed into the software. This is done by using the SCAMP Control Dialogs Channel Tab to place the correct values
into the C0
C3 and NOFF, NOFFPOLAR, and NGAIN boxes. Calibrated sensors supplied by
PME will have documentation that give these values. User supplied sensors must be
calibrated and the results placed here.